Stand alone or directed, short or long term monitoring,
measurement and evaluation of voltages, currents, active and reactive powers,
impedances, voltage outages, sags, asymmetry, flicker, harmonics on 16
channels simultaneously according to EN 61000-4-7, EN 61000-3-15, EN 50160
with the basic functions:
-
harmonic and spectrum analyzer
-
flicker meter
-
transient recorder
|
Signal conditioner side of TR-16
|
Main parameters:
-
16 isolated (3750VRMS 1 min.) analog and 16 digital inputs mounted
in rack system
-
wide variation of input units from 10 Vp up to 1000 Vp or from 2 mAp up
to 100 Ap connected directly or to the secondary of voltage or current
transformers or to capacitive voltage dividers or to clamp on current probes
-
frequency response: DC-100 kHz; overall accuracy 0.2 %
-
software directed input range selection (4 ranges/input unit)
analog and digital triggering from 8/16 channels
-
A/D conversion rate: 800 ksample /second
-
industrial computer housed in the signal conditioner box (iP166, 16 MB
RAM, 6GB HDD, 1.44 FDD, 9.5" colour LCD, modem)
-
automatic restart following voltage outage
-
FFT analysis, magnitude and phase up to 63rd
harmonic order
-
variable range spectrum analysis; DC-400Hz
up to DC-20 kHz
-
antialiasing filter
-
window functions are software selected
-
oscilloscope, registration and watch operation
modes
-
simultaneous measurement of flicker,
harmonics and transients
-
primary scaled active/reactive power, phase
and symmetrical components, asymmetry factors, true RMS, impedances, power
factor, distortion factor (THD), psophometric weighting of currents and
voltages
-
examine data in form of tables, diagrams,
plots, mathematical channels, vertical/horizontal zoom, statistics, correlation,
printing, plotting
-
flicker measurement and evaluation according
to EN 61000-3-15 and EN 50160. Pst, Plt statistics. Calibration of flickermeter
according to EN 61000-3-15. Manual or stand alone flicker analysis or watch
operation
-
identification of harmonic and flicker sources
-
transient recording (stand alone or manual)
on 16 analog and 16 digital input channels. Visualization, evaluation,
FFT analysis, printing, plotting, mathematical channels
-
software supported Power-quality report
-
data conversion in ASCII, EXCEL or optionally
in other format
-
outlets: serial and parallel ports, internal
modem
-
online data transfer through modem
-
MS Windows(tm) based evaluation
software
-
CE proof Supply: 230 V 50 Hz
-
Size:540x460x200 mm Weight: 20kg
|
Two quadrant drive PQ plot
|